Product web page: https://www.alorair.com/product/alorair-sentinel-hd55
Manuals
Connector Block
Image captured from https://community.home-assistant.io/t/automate-alorair-sentinel-hd55-dehumidifier/306084/6
Remote
Parts
Part |
Description
|
CPU |
HC32F072 (clone of STM32F072) (datasheet)
|
LCD Controller |
Holtek HT16C23
|
CAN Transceiver |
3PEAK TPT1051V
|
EEPROM |
BL24C02
|
Temperature sensor |
Unknown (markings erased)
|
Humidity sensor |
Unknown (no markings)
|
RJ-45 Pinout
Looking into the RJ-45 receptacle with the tab down, pin 1 is on the left.
Pin # |
Description
|
1 |
N/C
|
2 |
N/C
|
3 |
N/C
|
4 |
CANL
|
5 |
CANH
|
6 |
N/C
|
7 |
VCC (5V0)
|
8 |
GND
|
J1 Programming Connector
Pin # |
Description
|
1 |
nRST
|
2 |
VCC (3V3)
|
3 |
GND
|
4 |
SWCLK
|
5 |
SWDIO
|
CAN Bus
The dehumidifier and remote communicate using the CAN bus protocol at 50Kbps.
Currently, this decoding is based purely on using cantact-app, pushing buttons, and sending values. After I find a RJ45 breakout board, I'll monitor the actual data stream between the remote and the HD55.
Note that remote has several symbols that don't seem to be used. There is a tree symbol between the circled RH and house symbols, 'Time On' and 'Time Off' below the 'Draining' text, 'hr' text next to the percent symbol, a fan symbol to the right of the degrees Celsius symbol, and a bar graph in the lower right corner. The board has a footprint for a switch that is labeled 'WiFi new/old', so either the firmware supports the bar graph, or the same display is used on the WiFi version of the remote.
Tools
Notes
- Pressing the 'T' button will turn on the display backlight for 15 seconds or so, and also toggle the temperature display between Fahrenheit and Celsius. Unlike the other 6 buttons, it does not send a CAN message.
- The pump function (P button) is only available on the HDi90
- The temperature display is 0C (32F) minimum, 50C (122F) maximum, but temperatures over 37C (98F) do not display correctly, as there is no hundreds digit.
- The 7-segment display on the HD55 is supposed to display 'LO' if the temperature is under 0C (32F), but I have not found any bits that cause it to display on the remote.
- The up and down arrows send a 0x05 in byte 1, and a value in byte 2 that changes with each button press. Presumably it gets the initial value from the HD55/HDi90.
CAN Frame From Remote
CAN ID 0x123
Byte |
Description
|
0 |
Always 0x01
|
1 |
Value |
Button Status
|
0x00 |
No button pressed
|
0x01 |
Power
|
0x02 |
Pump (sends 0x01 in byte 2)
|
0x03 |
Continuous (sends 0x01 in byte 2)
|
0x04 |
Mode (sends 0x01 in byte 2)
|
0x05 |
Up or down arrow (sends value in byte)
|
|
2 |
0x00 (except when button pressed, see above)
|
3 |
RH on remote (20% = 0x14, 99% = 0x63)
|
4 |
Temperature on remote (in C, 0x00 = 0C, 0x30 = 48C)
|
5 |
Always 0x00
|
6 |
Always 0x00
|
7 |
Always 0x00
|
CAN Frame To Remote
CAN ID 0x3b0
Byte |
Description
|
0 |
RH value to display (20% = 0x14, 99% = 0x63)
|
1 |
Not used (?)
|
2 |
Not used (?)
|
3 |
Temperature to display (in C, 0x00 = 0C, 0x30 = 48C)
|
4 |
Not used (?)
|
5 |
Bit |
Description
|
0 (0x01) |
RH symbol on (indicates RH at dehumidifier)
|
1 (0x02) |
Circled RH + house on (indicates RH at remote)
|
2 (0x04) |
Unused (?)
|
3 (0x08) |
'Cont.' on (indicates continuous operation)
|
4 (0x10) |
'Draining' on (indicates drain pump is running)
|
5 (0x20) |
Unused (?)
|
6 (0x40) |
Display local RH and temp (set bit 1 also)
|
7 (0x80) |
Unused (?)
|
|
6 |
Not used (?)
|
7 |
Bit |
Description
|
0 (0x01) |
'E4' (indicates A5/A6 condensate pump overflow)
|
1 (0x02) |
'E5' (indicates refrigerant leak, may not apply to HD55/HDi90)
|
2 (0x04) |
'HI' (next to 'RT', indicates temperature > 105)
|
3 (0x08) |
'c0' (next to 'RT', indicates ?)
|
4 (0x10) |
'E1' (indicates humidity sensor error on HD55/HDi90)
|
5 (0x20) |
Unused (?)
|
6 (0x40) |
Unused (?)
|
7 (0x80) |
Unused (?)
|
|